IntroductionSimple Applications without Programming The ioLogik E2210 can convert a trigger event result directly into a digital alarm output. This can be set up using the ioAdmin UI to define an IF-THEN-ELSE Logic rule, eliminating the need to write programs for PCs or controllers. Software Event Counter Input and Pulse Output Each digital input can be independently configured for DI or Event Counter mode, and output can be independently configured for DO or Pulse Output mode. More info >> |
| • LAN: | |
| Ethernet | 1 x 10/100 Mbps, RJ45 |
| Protection | 1.5 KV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for I/O and Network), HTTP, CGI, SNTP |
| • Serial: | |
| Interface | RS-485-2w: Data+, Data-, GND |
| Serial Line Protection | 15 KV ESD for all signals |
| • Serial Communication Parameters: | |
| Baudrate | 1200 to 115200 bps |
| Data Bits | 8 |
| Stop Bits | 1 |
| Parity | None |
| Flow Control | None |
| Protocols | Modbus/RTU |
| • Digital Input: | |
| Channels | 12, source type |
| Sensor Type | NPN, Dry contact |
| I/O Mode | DI or Event Counter (up to 900 Hz) |
| Dry Contact | • Logic 0: short to GND • Logic 1: open |
| Wet Contact | • Logic 0: 0 to 3 VDC • Logic 1: 10 to 30 VDC (DI COM to DI) |
| Common Type | 12 points per COM |
| Isolation | 3K VDC or 2K Vrms |
| Counter Frequency | 900 Hz |
| Digital Filtering Time Interval | Software selectable |
| Over-voltage Protection | 36 VDC |
| • Digital Output: | |
| Channels | 8, sink type, 36 VDC, 200 mA |
| I/O Mode | DO or Pulse Output (up to 100 Hz) |
| Pulse Wave Width | 10 ms/100 Hz |
| Over-voltage Protection | 45 VDC |
| Over-current Limit | 400 mA (typical) |
| Over-temperature Shutdown | 175°C (min.) |
| Output Current Rating | Max. 200 mA per channel |
| Isolation | 3K VDC or 2K Vrms |
| • Physical Characteristics: | |
| Wiring | I/O cable max. 14AWG |
| • Environmental Limits: | |
| Operating Temperature | -10 to 60°C (14 to 140°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| • Power Requirements: | |
| Power Consumption | 282 mA typical @ 24 VDC |
| Power Input | 24 VDC nominal, 12 to 48 VDC |
| • Agency Approvals: | |
| EMI | FCC Part 15, CISPR (EN55022) class A |
| EMS | IEC 61000-4, IEC 61000-6 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| • Warranty: | |
| Warranty Period | 2 years |
| Details | See www.moxa.com/warranty |
Products
Next Step
Applications
- Truck loading system
- Active Ethernet IO server makes automated parking more efficient
- Active Ethernet IO used for SNMP-based remote site monitoring
- Power distributor uses Active Ethernet IO with Linux-based embedded computer for real-time SCADA system
- Supermarket uses Active Ethernet IO for customer interaction
- Enabling Active Alarms in Sewage Lift Station Monitoring Systems
- Small RTU Concept in Smart Grid for Broadband over Power Lines
- Intrusion Detection with SNMP and IP Video in Factory