ioLogik E2240
Active Ethernet I/O with 8 analog inputs and 2 analog outputs
![]() |
|
|
|
|
Features and Benefits
IntroductionCombination of Analog Input and Output The ioLogik E2240 is combination of analog input and output in one module. It supports sensors and actuators include pH, conductivity, pressure, flow, and valves. More info >> |
| • LAN: | |
| Ethernet | 10/100Mbps, RJ45 |
| Protection | 1.5KV magnetic isolation |
| Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP(MIB for I/O and Network), HTTP, SNTP |
| • Serial: | |
| Interface | RS-485-2w: Data+, Data-, GND |
| Serial Line Protection | 15KV ESD for all signals |
| • Serial Communication Parameters: | |
| Data Bits | 8 |
| Stop Bits | 1 |
| Parity | None |
| Flow Control | None |
| Protocols | Modbus/RTU |
| Speed | 1200 to 115200 bps |
| • Analog Input: | |
| Resolution | 16-bit |
| Input Range | ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA, 4 to 20 mA |
| Data Format | 16-bit integer (2's complement) |
| Accuracy | ± 0.1% FSR @ 25°C, ± 0.3% FSR @ -10 and 60°C |
| Sampling Rate (all channels) | 10 samples/sec (voltage) 6 samples/sec (current) |
| Input Impedence | 900k ohms |
| Built-in Resistor for Current Input | 106 Ohm |
| CMR @ 50/60 Hz | 95 dB min. |
| Zero Drift | ± 9 μV/°C |
| Span Drift | ± 25 ppm/°C |
| Optical Isolation Protection | 3K VDC or 2K Vrms |
| Channels | 8 |
| • Analog Output: | |
| Resolution | 12-bit |
| Output Range | 0 to 10V, 4 to 20 mA |
| Drive Voltage | 15 VDC for current output |
| Data Format | 12-bit |
| Accuracy | ± 0.1% FSR @ 25°C, ± 0.3% FSR @ -10 and 60°C |
| Zero Drift | ± 9 μV/°C |
| Span Drift | ± 25 ppm/°C |
| Load Resistor | < 250 ohms |
| Channels | 2 |
| • Physical Characteristics: | |
| Wiring | I/O cable max. 14AWG |
| • Environmental Limits: | |
| Operating Temperature | -10 to 60°C (14 to 140°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| • Power Requirements: | |
| Input Voltage | 24 VDC nominal, 12 to 48 VDC |
| DO Power | 24 VDC nominal, up to 30 VDC |
| • Agency Approvals: | |
| EMI | FCC Part 15, CISPR (EN55022) class A |
| EMS | IEC 61000-4, IEC 61000-6 |
| Safety | UL508 |
| Shock | IEC 60068-2-27 |
| Freefall | IEC 60068-2-32 |
| Vibration | IEC 60068-2-6 |
| • Warranty: | |
| Warranty Period | 2 years |
| Details | See www.moxa.com/warranty |