| • Inputs and Outputs |
| Analog Inputs |
4 channels |
| Configurable DIOs |
8 channels |
| Relay Outputs |
2 channels |
| • Analog Input |
| Resolution |
16 bits |
| I/O Mode |
Voltage / Current |
| Input Range |
0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA |
| Accuracy |
• ±0.1% FSR @ 25°C
• ±0.3% FSR @ -30 and 70°C
|
| Sampling Rate (all channels) |
100 samples/sec |
| Input Impedance |
200K ohms (min.) |
| Built-in Resistor for Current Input |
102 ohms |
| • Digital Input |
| Sensor Type |
Wet Contact (NPN or PNP) and Dry Contact |
| I/O Mode |
DI or Event Counter |
| Dry Contact |
• On: short to GND
• Off: open
|
| Wet Contact |
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
|
| Common Type |
4 points per COM |
| Isolation |
3K VDC or 2K Vrms |
| Counter Frequency |
900 Hz, power off storage |
| Digital Filtering Time Interval |
Software selectable |
| Over-voltage Protection |
36 VDC |
| Poweroff Counter |
Supports poweroff counter storage function |
| • Digital Output |
| Type |
Sink |
| I/O Mode |
DO or Pulse Output |
| Pulse Output Frequency |
1 kHz |
| Over-voltage Protection |
45 VDC |
| Over-current Protection |
2.6 A (4 channels @ 650 mA) |
| Over-temperature Shutdown |
160°C |
| Current Rating |
200 mA per channel |
| Isolation |
3K VDC or 2K Vrms |
| • Relay Output |
| Contact Rating |
1 A @ 30 VDC, 1 A @ 240 VAC, 1 A @ 110 VAC |
| Inductance Load |
2 A |
| Resistance Load |
5 A |
| Breakdown Voltage |
500 VAC |
| Relay On/Off Time |
10 ms, 5 ms (max.) |
| Initial Insulation Resistance |
1G min. @ 500 VDC |
| Expected Life |
100,000 times (Typical) |
| Initial Contact Resistance |
30 milli-ohms (max.) |
| Pulse Output |
20 operation times per minutes at rated load |
| Isolation |
3K VDC or 2K Vrms |
| • Cellular |
| Interface |
GSM/GPRS/EDGE |
| Band Options |
Quad-band GSM/GPRS/EDGE 850/900/1800/1900 MHz |
| GPRS Multi-Slot Class |
Class 10 |
| GPRS Terminal Device Class |
Class B |
| SMS |
Point-to-Point Text/PDU |
| SIM Control Voltage |
3 V |
| • LAN |
| Ethernet |
1 x 10/100 Mbps, RJ45 |
| Protection |
1.5 KV magnetic isolation |
| Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, SNTP |
| • Serial Communication |
| Interface |
1 x RS-232/422/485, software selectable (9-pin D-Sub male, or 5-contact terminal block) |
| Baudrate |
300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
| • Power Requirements |
| Power Input |
24 VDC nominal, 12 to 36 VDC |
| Power Consumption |
195 mA @ 24 VDC (always on) |
| • Physical Characteristics |
| Dimensions |
46.8 x 135 x 105 mm (1.84 x 5.31 x 4.13 in) |
| Weight |
495 g |
| • Environmental Limits |
| Operating Temperature |
Standard Model: -10 to 55°C (14 to 131°F)
Wide Temp. Model: -30 to 70°C (-22 to 158°F)
|
| Storage Temperature |
-40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity |
5 to 95% (non-condensing) |
| • Standards and Certifications |
| Safety |
UL 508 (Pending) |
| EMI |
FCC Part 15 Subpart B Class A, EN 55022 Class A |
| EMS |
IEC 61000-4, IEC 61000-6 |
| Mobile Network |
PTCRB |
| Shock |
IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Vibration |
IEC 60068-2-6 |
| • MTBF (mean time between failure) |
| Time |
196,561 hrs |
| Database |
Telcordia (Bellcore) |
| • Warranty |
| Warranty Period |
2 years |
| Details |
See www.moxa.com/warranty |