As of June 15, 2022, this site no longer supports Internet Explorer. Please use another browser for the best experience on our site.
MOXA

Rugged Controllers & I/Os

Rail, wind power, and offshore applications demand system reliability and stability, even in harsh environments. Our rugged controllers and I/O products are designed to perform in extreme conditions while providing versatile data acquisition and control capabilities.

65M-PW0075-CT-T
ioPAC 6500 Series (65M) Power Modules

ioPAC 6500 power module, 24 VDC, 75 W, -40 to 75°C operating temperature, conformal coating

System Power Parameters
  • Power Connector

    • Screw-fastened Euroblock terminal
  • No. of Power Inputs

    • 1
  • Input Voltage

    • Nominal value: 24 VDC
      Acceptable range: 21.6 to 26.4 VDC
  • Input Current

    • 4 A (max.)
  • Inrush Current

    • 20 A (max.)
  • Internal Fuse Rating

    • 10 A
  • Output Voltage

    • 12 VDC
  • Output Current

    • 6.25 A (max.)
  • Output Power

    • 75 W (max.)
  • Output Hold-up Time

    • 10 ms (min.)
  • Output Startup Delay Time

    • 100 ms (max.)
  • Over-Voltage Protection

    • 15.6 VDC (max.)
  • Over-Current Protection

    • 9 A (min.)
  • Efficiency

    • 87%
  • Isolation

    • 3k VDC (input to output)
      3k VDC (system to field power)
Field Power Parameters
  • Power Connector

    • Screw-fastened Euroblock terminal
  • No. of Power Inputs

    • 1
  • Input Voltage

    • Nominal value: 24 VDC
      Acceptable range: 21.6 to 26.4 VDC
  • Input Current

    • 3 A (max.)
  • Internal Fuse Rating

    • 8 A
  • Output Voltage

    • 3 A (max.)
      [Input Voltage - 0.4] VDC (max., matching diode drop at 3 A)
  • Over-voltage Protection

    • 29 VDC (max.)
  • Over-current Protection

    • 5 A (min.)
Physical Characteristics
  • Housing

    • Plastic
  • Dimensions

    • 42 x 177 x 149.4 mm (1.65 x 6.97 x 5.88 in)
  • Weight

    • 713 g (1.57 lb)
  • Installation

    • DIN-rail mounting
      Rack mounting (with optional kit)
Standards and Certifications
  • EMC

    • EN 55032/35
      EN 61000-6-2/-6-4
  • EMI

    • CISPR 32, FCC Part 15B Class A
  • EMS

    • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
      IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
      IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV
      IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV
      IEC 61000-4-6 CS: Power: (DC) 10 Vrms; Signal: 10 Vrms
      IEC 61000-4-8 PFMF: 30 A/m
  • Safety

    • UL 61010-1
      UL 61010-2-201
  • Shock

    • IEC 60068-2-27
      Half sine wave; acceleration: 15 g; time: 11 ms
  • Vibration

    • IEC 60068-2-6
      DIN-rail mounted:
      7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz)
      Rack mounted (with optional kit):
      7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
  • Package Vibration Test

    • ISTA 1A
  • Package Drop Test

    • ISTA 1A
MTBF
  • Time

    • 954,606 hrs
  • Standards

    • Telcordia Standard SR-332
Environmental Limits
  • Operating Temperature

    • -40 to 75°C (-40 to 167°F)
      Note: Proper airflow is required in an environment with temperature > 65°C
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 5 to 95% (non-condensing)
  • Altitude

    • Up to 2000 m
Warranty