As of June 15, 2022, this site no longer supports Internet Explorer. Please use another browser for the best experience on our site.
MOXA

Rugged Controllers & I/Os

Rail, wind power, and offshore applications demand system reliability and stability, even in harsh environments. Our rugged controllers and I/O products are designed to perform in extreme conditions while providing versatile data acquisition and control capabilities.

65M-2901-CT-T
ioPAC 6500 Series (65M) I/O Modules

ioPAC 6500 DO module with 32 channels, 24 VDC, -40 to 75°C operating temperature, conformal coating

Input/Output Interface
  • Digital Output Channels

    • 32
  • Isolation

    • 65M-3600-CT-T/65M-3610-CT-T/65M-4820-CT-T:
      System: 3k VDC
      Signal: 1k VDC (between group for 1 min)
      All other models:
      System: 3k VDC
      Signal: 3k VDC
Digital Inputs
  • I/O Type

    • Sink
      (Internal/external sensor supply for dry contact)
  • I/O Mode

    • DI or event counter
      (channels 1 to 8, group configurable by software)
  • Input Voltage

    • On: 11 to 30 VDC
      Off: 0 to 5 VDC
  • Input Current (voltage on)

    • 2.35 mA ± 20% per channel
  • Counter Frequency

    • Square wave: 0 to 10 kHz
  • Digital Filtering Time Interval

    • Software configurable
  • Diagnostics

    • Input Wire-break Detection (current: 50 µA max., delay: 20 ms)
      Internal Field Circuit Supply Detection (17.5 VDC, 16 to 19 VDC)
Digital Outputs
  • I/O Type

    • Source
  • I/O Mode

    • DO or pulse output
      (channel 1 to 8, group configurable by software)
  • Pulse Duration

    • 500 μs
  • Protection

    • Output Short-circuit Protection
      Common Power Input Over-voltage Protection
      Inductive Load Shutdown Voltage Protection
  • Diagnostics

    • Wire Break Detection (on state, output current < 3 mA)
      Wire Break Detection (off state, output load impedance > 58 kilo-ohms)
      Output Short-Circuit Detection (output current > 0.87 A, range: 0.64 to 1.2 A)
      External Power Detection (17.5 VDC, 16 to 19 VDC)
      Failsafe Configuration (hold last/failsafe state)
Analog Inputs
  • I/O Mode

    • 65M-3600-CT-T: Current
      65M-3610-CT-T: Voltage
  • I/O Type

    • Differential
  • Input Range

    • 65M-3600-CT-T:
      0 to 20 mA
      4 to 20 mA
      65M-3610-CT-T:
      0 to 10 V
      1 to 5 V
  • Overload Permitted on Inputs

    • 65M-3600-CT-T: ±30 mA
      65M-3610-CT-T: ±12 V
  • Measurement Resolution

    • 65M-3600-CT-T:
      2 μA (0 to 20 mA)
      1.6 μA (4 to 20 mA)
      65M-3610-CT-T:
      1 mV (0 to 10 V)
      0.4 mV (1 to 5 V)
  • Accuracy

    • ±0.1% FSR @ 25°C
      ±0.3% FSR @ -40 to 75°C
  • Conversion Time

    • 100 ms
  • Rejection Ratio

    • Normal mode: > 60 dB @ 60 Hz (min.), conversion time: 100 ms
      Common mode: > 90 dB @ 60 Hz (min.), conversion time: 100 ms
  • Input Impedance

    • 65M-3600-CT-T: 250 ohms
      65M-3610-CT-T: 1 mega-ohms
  • Diagnostics

    • 65M-3800-3810-CT-T:
      Input Underflow/Overflow Detection
      65M-3600-CT-T:
      Internal Loop Power Detection (17.5 VDA, 16 to 19 VDC)
      Input Short-circuit Detection
      65M-3600-CT-T (in 4 to 20 mA mode):
      Input Wire-break Detection (delay: 0.8 s)
      65M-3610-CT-T:
      Input Wire-break Detection (delay:1.6 s max)
Analog Outputs
  • I/O Mode

    • Voltage/Current
  • Output Range

    • 0 to 10 V
      1 to 5 V
      0 to 20 mA
      4 to 20 mA
  • Converter Resolution

    • 16-bit
  • Accuracy

    • ±0.1% FSR @ 25°C
      ±0.3% FSR @ -40 to 75°C
  • Output Refresh Time

    • 16 ms
  • Output Impedance

    • Voltage mode:
      1 kilo-ohms (min.)
      Current mode:
      750 ohms (max.)
  • Diagnostics

    • Output Short-circuit Detection (voltage)
      Failsafe Configuration (hold last/failsafe state)
      Output Wire-break Detection (current)
Terminal Blocks
  • Connector

    • Screw-fastened terminal block
  • Dimensions

    • 42.3 x 102.38 x 80.8 mm (1.67 x 4.03 x 3.18 in)
  • Weight

    • 164 g (0.36 lb)
Power Consumption
  • System Power

    • 65M-1900-CT-T:
      0.019 A @ 24 VDC (without internal field circuit supply)
      0.115 A @ 24 VDC (32-channel dry contact with internal field circuit supply)
      65M-2901-CT-T:
      0.005 A @ 24 VDC
      65M-3600-CT-T:
      0.053 A @ 24 VDC (without internal loop power)
      0.466 A @ 24 VDC (16-channel 20 mA current input with internal loop power)
      65M-3610-CT-T:
      0.038 A @ 24 VDC
      65M-4820-CT-T:
      0.022 A @ 24 VDC (without external load)
      0.266 A @ 24 VDC (4 channels with 20 mA current output)
  • Field Power

    • 65M-1900-CT-T/65M-2901-CT-T:
      0.068 A @ 12 VDC
      65M-3610-CT-T/65M-4820-CT-T:
      0.069 A @ 12 VDC
      65M-3600-CT-T:
      0.073 A @ 12 VDC
Physical Characteristics
  • Housing

    • Plastic
  • Dimensions

    • 42 x 116 x 130 mm (1.65 x 4,57 x 5.12 in)
  • Weight

    • 254 g (0.56 lb)
Environmental Limits
  • Operating Temperature

    • -40 to 75°C (-40 to 167°F)
      Note: Proper airflow is required in an environment with temperature > 65°C.
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 5 to 95% (non-condensing)
  • Altitude

    • Up to 2000 meters Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
  • EMC

    • EN 55032/35
      EN 61000-6-2/-6-4
  • EMI

    • CISPR 32, FCC Part 15B Class A
  • EMS

    • IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
      IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
      IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV
      IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV
      IEC 61000-4-6 CS: Power: (DC) 10
      Vrms; Signal: 10 Vrms
      IEC 61000-4-8 PFMF: 30 A/m
  • Safety

    • UL 61010-1
      UL 61010-2-201
  • Shock

    • IEC 60068-2-27
      Half sine wave; acceleration: 15 g; time: 11 ms
  • Vibration

    • IEC 60068-2-6
      DIN-rail mounted:
      7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz)
      Rack mounted (with optional kit):
      7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
MTBF
  • Time

    • 2,007,795 hrs
  • Standards

    • Telcordia Standard SR-332
Warranty
Added To Bag
You have some items waiting in your bag; click here to finish your quote!
Feedback