As of June 15, 2022, this site no longer supports Internet Explorer. Please use another browser for the best experience on our site.
MOXA

Modbus TCP Gateways

Whether single or multiple serial ports, Moxa’s Modbus TCP gateway solutions convert data in networks between Modbus RTU/ASCII, Modbus TCP, DNP3, CANopen, J1939, PROFIBUS, BACnet/IP, IEC 101/104, and IEC 61850, making configuration, troubleshooting, and conversion quick and easy.

MGate 5192-T
MGate 5192 Series

MGate 5192-T

Ethernet Interface
  • 10/100BaseT(X) Ports (RJ45 connector)

    • 2
      Auto MDI/MDI-X connection
  • Magnetic Isolation Protection

    • 1.5 kV (built-in)
Ethernet Software Features
  • Industrial Protocols

    • IEC 61850 MMS Client
      Modbus TCP Server
      IEC 60870-5-104 Server
      DNP3 TCP/UDP Outstation
  • Configuration Options

    • Web Console (HTTPS)
      Device Search Utility (DSU)
  • Management

    • ARP
      DHCP Client
      DNS
      HTTP
      HTTPS
      SMTP
      SNMP Trap
      SNMPv1/v2c/v3
      TCP/IP
      UDP
  • MIB

    • RFC1213, RFC1317
  • Time Management

    • NTP Client
Security Functions
  • Authentication

    • Local database
  • Encryption

    • HTTPS
      AES-128
      AES-256
      SHA-256
  • Security Protocols

    • SNMPv3
      SNMPv2c Trap
      HTTPS (TLS 1.3)
Serial Interface
  • No. of Ports

    • 1
  • Connector

    • DB9 male
  • Serial Standards

    • RS-232/422/485
  • Baudrate

    • 300 bps to 921.6 kbps
  • Data Bits

    • 7, 8
  • Parity

    • None
      Even
      Odd
      Space
      Mark
  • Stop Bits

    • 1, 2
  • Flow Control

    • RTS Toggle (RS-232 only)
      RTS/CTS
  • RS-485 Data Direction Control

    • Automatic Data Direction Control (ADDC)
  • Pull High/Low Resistor for RS-485

    • 1 kilo-ohm, 150 kilo-ohms
      software configurable
  • Terminator for RS-485

    • 120 ohms
      software configurable
  • Isolation

    • 2 kV (built-in)
Serial Signals
  • RS-232

    • TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
  • RS-422

    • Tx+, Tx-, Rx+, Rx-, GND
  • RS-485-2w

    • Data+, Data-, GND
  • RS-485-4w

    • Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
  • Industrial Protocols

    • Modbus RTU/ASCII Server
      IEC 60870-5-101 Server
      DNP3 Serial Outstation
IEC 61850
  • Mode

    • MMS Client
  • Max. No. of Server Connections

    • 32
  • Max. No. of Data Objects

    • 5000 points
Modbus TCP
  • Mode

    • Server
  • Functions Supported

    • 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Max. No. of Client Connections

    • 16
  • Max. No. of Data Tags

    • 5000 tags
Modbus RTU/ASCII
  • Mode

    • Server
  • Functions Supported

    • 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Max. No. of Client Connections

    • 1
  • Max. No. of Data Tags

    • 5000 tags
DNP3 TCP/UDP
  • Mode

    • Outstation
  • Objects Supported

    • Binary inputs
      Analog inputs
      Counters
      Frozen counters
      Binary outputs
      Analog outputs
  • Max. No. of Client Connections

    • 1
  • Protocol Security

    • Secure Authentication v5
  • Max. No. of Objects

    • 5000 points
DNP3 Serial
  • Mode

    • Outstation
  • Objects Supported

    • Binary inputs
      Analog inputs
      Counters
      Frozen counters
      Binary outputs
      Analog outputs
  • Max. No. of Client Connections

    • 1
  • Max. No. of Objects

    • 5000 points
IEC 60870-5-101
  • Mode

    • Server (balanced/unbalanced)
  • Objects Supported

    • Single point
      Double point
      Step position
      Bit string of 32 bit
      Measured value (normalized)
      Measured value (scaled)
      Measured value (floating)
      Integrated totals
  • Max. No. of Client Connections

    • 1
  • Max. No. of Information Objects

    • 5000 points
IEC 60870-5-104
  • Mode

    • Server
  • Objects Supported

    • Single point
      Double point
      Step position
      Bit string of 32 bit
      Measured value (normalized)
      Measured value (scaled)
      Measured value (floating)
      Integrated totals
  • Max. No. of Client Connections

    • 32
  • Max. No. of Information Objects

    • 5000 points
Memory
  • microSD Slot

    • Up to 32 GB (SD 2.0 compatible)
Power Parameters
  • Input Voltage

    • 12 to 48 VDC
  • Input Current

    • 455 mA (max)
  • Power Connector

    • Spring-type Euroblock terminal
Relays
  • Contact Current Rating

    • Resistive load: 2 A @ 30 VDC
Physical Characteristics
  • Housing

    • Metal
  • IP Rating

    • IP30
  • Dimensions

    • 25 x 90 x 129.6 mm (0.98 x 3.54 x 5.1 in)
  • Weight

    • 294 g (0.65 lb)
Environmental Limits
  • Operating Temperature

    • -40 to 75°C (-40 to 167°F)
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 5 to 95% (non-condensing)
Standards and Certifications
  • Safety

    • EN 61010-2-201
      UL 61010-2-201
  • EMC

    • EN 61000-6-2/-6-4
  • EMI

    • FCC Part 15B Class A
  • EMS

    • IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
      IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m
      IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
      IEC 61000-4-5 Surge: Power: 2 kV; Signal: 4 kV
      IEC 61000-4-6 CS: 10 V/m
      IEC 61000-4-8 PFMF: 100 A/m
  • Shock

    • IEC 60068-2-27
  • Vibration

    • IEC 60068-2-6
      IEC 60068-2-64
  • Power Substation

    • IEEE 1613
      IEC 61850-3
  • International Approval

    • UKCA
      KC
MTBF
  • Time

    • 1,240,821 hrs
  • Standards

    • Telcordia SR332
Warranty
Added To Bag
You have some items waiting in your bag; click here to finish your quote!
Feedback