Hi! Please sign in Home >  Products & Solutions  > Remote Automation > Programmable Controller Series > Modular Programmable Controller > System Module > ioPAC 8600 Series Expansion Modules

ioPAC 8600 Series Expansion Modules

I/O Modules for ioPAC 8600 series modular programmable controllers

Features and Benefits

  • 86M-1620D-T: 16 digital inputs, 24 to 110 VDC, channel LED, sink type
  • 86M-1832D-T: 8 channel-to-channel isolated DIs, 24 VDC, channel LED, sink/source type
  • 86M-2604D-T: 6 relays, channel LED, form A (N.O.) type
  • 86M-2830D-T: 8 channel-to-channel isolated DOs, 24 VDC, channel LED, sink-type
  • 86M-4420-T: 4 analog outputs, 0 to 10 V or -10 to 10 V or 0 to 20 mA or 4 to 20 mA
  • 86M-5212U-T: 2-port 2-wire Ethernet switch
  • 86M-5250-T: 2 CAN ports, channel LED

Introduction

Moxa’s 86M series modules with ch-to-ch isolated DIs, ch-to-ch isolated DOs, relays, and AOs provide more I/O options for the ioPAC 8600 series. Combined with 85M modules, enough options are now available to allow users to select the best I/O combination for their target application. All 86M modules are designed for railway industry applications, and as such are compliant with EN 50121-3-2, EN 50121-4, and EN 50155. In addition, the modules support a wide operating temperature range of -40 to 75°C.
 
86M-1832D-T Specifications
Inputs and Outputs
Digital Inputs 8 channels
Isolation To system: 3k VDC or 2k Vrms
Channel-to-channel: 1k VDC
Digital Input
Sensor Type Wet contact (NPN or PNP)
I/O Mode DI, counter, or frequency
Wet Contact (DI+ to DI-) • On: 10 to 30 VDC
• Off: 0 to 3 VDC
Counter Frequency 5 kHz
Digital Filtering Time Interval Software selectable (by 0.1 ms)
Physical Characteristics
Wiring I/O cable, 16 AWG (max.)
Connector Spring-type terminal block
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 12.6 mA @ 24 VDC
MTBF (mean time between failures)
Time 1,149,108 hrs
Standard Telcordia SR332
 
86M-2830D-T Specifications
Inputs and Outputs
Digital Outputs 8 channels
Isolation To system: 3k VDC or 2k Vrms
Channel-to-channel: 1k VDC
Digital Output
Type Sink
I/O Mode DO or PWM
Pulse Output Frequency 1 kHz
Short Circuit Protection 750 mA @ 25°C
Over-Voltage Protection 41 VDC
Over-Current Protection 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown 175°C (typical), 150°C (min.)
Current Rating 200 mA per channel
Physical Characteristics
Wiring I/O cable, 16 AWG (max.)
Connector Spring-type terminal block
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 76.7 mA @ 24 VDC
MTBF (mean time between failures)
Time 1,766,037 hrs
Standard Telcordia SR332
 
86M-2604D-T Specifications
Inputs and Outputs
Relays 6 channels
Isolation To System: 3k VDC or 2k Vrms
Relay
Type Form A (N.O.)
I/O mode DO or PWM
Pulse Output Frequency 0.33 Hz
Contact Current Rating Resistive Load: 5 A @ 30 VDC, 250 VAC
Relay On/Off Time 10 ms (max.)
Initial Insulation Resistance 1000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance 5,000,000 operations
Electrical Endurance 60,000 operations @ 5 A resistive load
Contact Resistance 100 milli-ohms (max.)
Physical Characteristics
Wiring I/O cable, 16 AWG (max.)
Connector Spring-type terminal block
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 127 mA @ 24 VDC
MTBF (mean time between failures)
Time 4,173,843 hrs
Standard Telcordia SR332
 
86M-4420-T Specifications
Inputs and Outputs
Analog Outputs 4 channels
Isolation To system: 3k VDC or 2k Vrms
Analog Output
Resolution 12 bits
Output range 0 to 10 V, -10 to 10 V, 0 to 20 mA, 4 to 20 mA
I/O mode Static or Waveform mode
Voltage Output 10 mA (max.)
Accuracy ±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Current Load Resistance Internal Power: 400 ohms
External 24 VDC Power: 1000 ohms
Update Rate Software polling or waveform mode
Waveform Type Sine, Triangle, Square
Wavemode Frequency 125 Hz
Physical Characteristics
Wiring I/O cable, 16 AWG (max.)
Connector Spring-type terminal block
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 94.2 mA @ 24 VDC (voltage)
143.8 mA @ 24 VDC (current)
MTBF (mean time between failures)
Time 2,409,345 hrs
Standard Telcordia SR332
 
86M-1620D-T Specifications
Inputs and Outputs
Digital Inputs 16 channels
Isolation To system:
3k VDC or 2k Vrms
Digital Input
Type PNP
I/O mode DI
Logic Definition • On: channel voltage > 0.3 x (external power voltage)
• Off: channel voltage < 0.15 x (external power voltage)
Scan Period 8 ms (typ.)
Scan on Time 0.5 ms
Debouncing Function Software disable/enable
Debouncing Time 1 to 15 ms (software-selectable)
Common Type 8 points per COM
Physical Characteristics
Wiring I/O cable, 16 AWG (max.)
Connector Spring-type terminal block
Channel LED Yes
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 12.6 mA @ 24 VDC
MTBF (mean time between failures)
Time 1,115,244 hrs
Standard Telcordia SR332
 
86M-5212U-T Specifications
Ethernet Communication
Interface Two 2-wire Ethernet ports
Isolation To system: 3k VDC or 2k Vrms
Standards
Supported Standards 100BASE-TX IEEE 802.3u
10BASE-T IEEE 802.3
100 Mbps BroadR-Reach®
10 Mbps BroadR-Reach®
Physical Characteristics
Wiring CAT 5 standard cable with M12 D-code male connection
Connector M12 (D-code, female) x 2
Channel LED Yes
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 578 mA @ 3.3 VDC
MTBF (mean time between failures)
Time 2,498,942 hrs
Standard Telcordia SR332
 
86M-5250-T Specifications
Serial Communication
Interface 2 CAN ports
Isolation To system: 3k VDC or 2k Vrms
CAN Bus Communication
Protocols CAN 2.0A
CAN 2.0B
CANopen DS301, V4.02
CANopen DS401
Speed 10/20/50/125/250/500/800 kbps, 1 Mbps
Termination Resistor N/A, 120 ohms (by DIP)
Physical Characteristics
Connector DB9 male
Channel LED Yes
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Power Requirements
Input Current 60 mA @ 24 VDC
MTBF (mean time between failures)
Time 3,306,609 hrs
Standard Telcordia SR332
 
Common Specifications
Environmental Limits
Operating Temperature -40 to 75°C (-40 to 176°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Shock IEC 60068-2-27
Vibration IEC 60068-2-6
Standards and Certifications
Safety UL 61010
EMC EN 55032/24
EMI FCC Part 15 Subpart B Class A, CISPR 32
EMS IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS:
80 MHz to 1000 MHz: 3 V/m
1400 MHz to 2100 MHz: 3 V/m
2100 MHz to 2700 MHz: 1 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L);
Rail Traffic EN 50155*, EN 50121-4
*This product is suitable for rolling stock railway applications, as defined by the EN 50155 standard. For a more detailed statement, click here
www.moxa.com/doc/specs/EN_50155_Compliance.pdf
Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty

To request a quote, indicate which items you are interested in below and click "Get a Quote".

Available Models

  Model No. Description
86M-1620D-T 16 DIs, sink, 24 to 110 VDC, channel LED, -40 to 75°C operating temperature
86M-1832D-T 8 DIs, sink/source, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature
86M-2604D-T 6 relays, form A (N.O.), channel LED, -40 to 75°C operating temperature
86M-2830D-T 8 DOs, sink, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature
86M-4420-T 4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA, -40 to 75°C operating temperature
86M-5212U-T 2-port 2-wire Ethernet switch, -40 to 75°C operating temperature
86M-5250-T 2 CAN ports, -40 to 75°C operating temperature

     